Add to Cart
Discover unparalleled power protection and continuity with our state-of-the-art Online Uninterruptible Power Supply (UPS) designed to meet the demanding needs of today’s technological environments. Our UPS product stands out with its innovative modular design, ensuring that your critical systems remain operational even in the face of power disruptions. This product summary delves into the specifics of our UPS, highlighting its superior features and the benefits it offers to various applications. At the heart of our UPS's reliability is its Rack Mounted Modular architecture, which not only provides a scalable power solution adaptable to varying loads but also facilitates ease of maintenance and expansion. The modular ups systems approach allows for redundancy, ensuring no single point of failure can compromise your power infrastructure. This modular design means that you can increase power protection as your demand grows, making it a future-proof investment for businesses of all sizes. | ![]() |
![]() |
|
Model CNM | 020/10 | 030/15 | 040/20 | 040/10 | 045/15 | 060/15 | 080/20 | 090/15 | 120/20 |
Rate Power | 20KVA/20KW | 30KVA/30KW | 40KVA/40KW | 40KVA/40KW | 45KVA/45KW | 60KVA/60KW | 80KVA/80KW | 90KVA/90KW | 120KVA/120KW |
Main input | |||||||||
Input | 3P5W(3P+N+PE) | ||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Rate Freq | 50/60Hz | ||||||||
Input PF | >0.99 | ||||||||
Current Distortion | THDi<3%(100%Linear load) | ||||||||
Voltage Range | 304-478VAC(L-L)full load;304-228VAC(L-L)power derate from 100%to 75% | ||||||||
Freg.Range | 40-70Hz | ||||||||
Battery | |||||||||
Rate voltage | ±240VDC(adjustable for 32-44 sections) | ||||||||
Charging Capacity | 20%*Pout | ||||||||
Charging Accuracy | ±1% | ||||||||
Bypass | |||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Voltage Range | Range:-40%-+25%,Settable,default-20%~+15% | ||||||||
Overload | 110%,long time operation;110%<load<125%,5 mins 125%<load<150%,1min;>150%,1second | ||||||||
Inverter | |||||||||
Rate Voltage | 380/400/415VAC(L-L);220/230/240VAC(L-N) | ||||||||
Rate Freq | 50/60Hz | ||||||||
Output PF | 1 | ||||||||
Voltage Accuracy | ±1.0% | ||||||||
load Response | <5%(20%-80%-20%step load) | ||||||||
Recovery Time | <20ms(0%-100%-0%step load) | ||||||||
Output THDu | <1%(linear load),<5%(non-linear load according to IEC 62040-3) | ||||||||
Overload | 110%,1 hour;125%,10 mins;150%,1min;>150%,200ms | ||||||||
Frequency Accuracy | 0.1% | ||||||||
Synchronize Window | Settable,±0.5Hz-±5Hz,default±3Hz | ||||||||
Slew Rate | Settable,0.5Hz/S-3Hz/S,default 0.5Hz/S | ||||||||
Phase Accuracy | 120°±0.5° | ||||||||
System | |||||||||
Efficiency | Normal Mode≥96%;Battery Mode≥96% | ||||||||
Display | LED+7inch touch LCD | ||||||||
Certification-Safety | IEC62040-1,IEC60950-1 | ||||||||
Certification-EMS | IEC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);IEC61000-4-4(EFT);IEC61000-4-5(Surge) | ||||||||
IP Degree | IP20 | ||||||||
Configuration | USB,RS232,RS485,Dry contact,Cold start | ||||||||
Option | SNMP card,AS400 card,Parallel kit,LBS,Air filter,Bottom entry kit,Wheels kit | ||||||||
Environment | 0-40℃(operation);-25~70(storage);0-95%(Humidity,non-condensing) | ||||||||
Noise(dB)(1meter) | 65dB @100%load,62dB @45%load | ||||||||
Dimension | |||||||||
Cabinet(W*D*H)mm | 482*700*396(9U, wheels not included) | 482*700*662(15U, wheels not included) | 482*700*840(19U, wheels not included) | ||||||
Module(W*D*H)mm | 440*555*85(2U) |
Certification